Maximum fresh air airflow rate (renewal) |
150 m³/h |
Maximum airflow rate (indoor recirculation) |
300 m³/h |
Airflow regulation range |
from 80 to 300 m³/h |
Nominal condensing capacity |
31,44 l/24h with 150 m³/h, 26°C and 60%R.H. room and 150 m³/h, 30°C and 60%R.H. fresh air, at nominal water flow conditions (400 l/h) and at the temperature of 15°C |
Total refrigerant capacity in dehumidification |
1,36 kW with 150 m³/h, 26°C and 60%R.H. room and 150 m³/h, 30°C and 60%R.H. fresh air, at nominal water flow conditions (400 l/h) and at the temperature of 15°C |
Total refrigeration capacity in integration |
1,193 kW with 150 m³/h, 26°C and 60%R.H. room and 150 m³/h, 30°C and 60%R.H. fresh air, at nominal water flow conditions (400 l/h) and at the temperature of 15°C |
Useful static pressure in dehumidification and/or integration + ventilation with maximum flow (150 m³/h fresh air + 150 m³/h air recirculation = 300 m³/h supply air) (with G4 filters) |
240 Pa |
Useful static pressure in ventilation only with maximum flow (150 m³/h fresh air) (with G4 filters) |
290 Pa |
Useful static pressure in discharge with maximum flow (150 m³/h fresh air) (with G4 filters) |
330 Pa |
Nominal water flow |
400 l/h |
Summer operation |
water at nominal temperature of 15°C |
Water pressure drop (at nominal water flow) |
7kPa |
Sound pressure level (at 1m) |
43 dB (A) (in ventilation only, at maximum flow rate of 105 m³/h and with available pressure head of 50 Pa) |
Filters |
G4 class removable (no.3) - ISO COARSE > 65 % |
condensate siphon drain (with working depth of at least 40 mm) |
1 |
Cooling circuit complete with thermostatic expansion valve and dehydrator filter |
|
Control board equipped with microprocessor electric control, interfaceable with ModBus RS485 protocol, and control terminal block |
POWER SUPPLY |
|
Voltage |
230 V - 50 Hz |
Maximum absorbed power |
0,75 kW |
Maximum absorbed current |
5,6 A |
POWER CONSUMPTION IN VENTILATION: supply 150 m³/h / extract 150 m³/h |
|
Absorbed power, 50 Pa USP |
64,2 W (24,6+23,6+16) |
Absorbed current, 50 Pa USP |
0,41 A (0,17+0,16+0,08) |
Absorbed power, 100 Pa USP |
78 W (31,6+30,4+16) |
Absorbed current, 100 Pa USP |
0,53 A (0,23+0,22+0,08) |
Absorbed power, 150 Pa USP |
92,7 W (39,1+37,6+16) |
Absorbed current, 150 Pa USP |
0,65 A (0,29+0,28+0,08) |
Absorbed power, 200 Pa USP |
107,0 W (46,5+45,0+16) |
Absorbed current, 200 Pa USP |
0,78 A (0,36+0,35+0,08) |
POWER CONSUMPTION IN DEHUMIDIFICATION AND/OR INTEGRATION + VENTILATION WITH COMPRESSOR ON: supply 300 m³/h / extract 150 m³/h / recirculation 150 m³/h *water flow and water temperature at nominal conditions (400 l/h at 15°C) |
|
Absorbed power, 50 Pa USP |
275,9 W (24,6+35,3+16+200) |
Absorbed current, 50 Pa USP |
2,71 A (0,17+0,26+0,08+2,2) |
Absorbed power, 100 Pa USP |
291,6 W (31,6+44,0+16+200) |
Absorbed current, 100 Pa USP |
2,84 A (0,23+0,33+0,08+2,2) |
Absorbed power, 150 Pa USP |
308,3 W (39,1+53,2+16+200) |
Absorbed current, 150 Pa USP |
2,98 A (0,29+0,41+0,08+2,2) |
Absorbed power, 200 Pa USP |
325,1 W (46,5+62,6+16+200) |
Absorbed current, 200 Pa USP |
3,14 A (0,36+0,51+0,08+2,2) |
POWER CONSUMPTION INTEGRATION + WINTER MODE VENTILATION WITH COMPRESSOR OFF: supply 300 m³/h / extract 150 m³/h / recirculation 150 m³/h |
|
Absorbed power, 50 Pa USP |
75,9 W (24,6+35,3+16) |
Absorbed current, 50 Pa USP |
0,51 A (0,17+0,26+0,08) |
Absorbed power, 100 Pa USP |
91,6 W (31,6+44,0+16) |
Absorbed current, 100 Pa USP |
0,64 A (0,23+0,33+0,08) |
Absorbed power, 150 Pa USP |
108,3 W (39,1+53,2+16) |
Absorbed current, 150 Pa USP |
0,78 A (0,29+0,41+0,08) |
Absorbed power, 200 Pa USP |
125,1 W (46,5+62,6+16) |
Absorbed current, 200 Pa USP |
0,94 A (0,36+0,51+0,08) |
DEHUMIDIFICATION CAPACITY: supply 300 m³/h / extract 150 m³/h / recirculation 150 m³/h - Water flow and water temperature at nominal conditions (400 l/h a 15°C) - Fresh air: 30°C and 60%R.H. / Room: 26°C e 60%R.H. |
|
Refrigerant capacity |
1,36 kW (Coils + Heat exchanger) |
Condensation capacity |
31,44 l/24h (Coils + Heat exchanger) |
DEHUMIDIFICATION CAPACITY: supply 300 m³/h / recirculation: 300 m³/h / Total recirculation - water flow and water temperature at nominal condition (400 l/h a 15°C) - Room: 26°C and 60%R.H. |
|
Refrigerant capacity |
0,95 kW (Batterie | Coils) |
Condensation capacity |
20,89 l/24h (Batterie | Coils) |
COOLING CAPACITY: supply 300 m³/h / extract 150 m³/h / recirculation 150 m³/h - water flow and water temperature at nominal condition (400 l/h a 15°C) - Fresh air: 30°C and 60%R.H. / Room: 26°C and 60%R.H. |
|
Maximum power |
1,3 kW (Coils + Heat exchanger) |
COOLING CAPACITY: supply 300 m³/h / recirculation 300 m³/h / Total recirculation - water flow and water temperature at nominal condition (400 l/h a 15°C) - Room: 26°C and 60%R.H. |
|
Maximum power |
0,92 kW (Coils) |
HEATING CAPACITY: supply 300 m³/h / extract 150 m³/h / recirculation 150 m³/h - water flow and water temperature at nominal condition (400 l/h a 35°C) - Fresh air: -5°C and 80%R.H. / Room: 20°C and 50%R.H. |
|
Thermal power |
1,9 kW (Coils + Heat exchanger) |
HEATING CAPACITY: supply 300 m³/h / extract 150 m³/h / recirculation 150 m³/h - water flow and water temperature at nominal condition (400 l/h a 35°C) - Fresh air: -5°C and 80%R.H. / Room: 20°C and 50%R.H. |
|
Thermal power |
1,19 kW (Coil) |
DIMENSIONS |
|
Unit dimensions |
800 mm x 800 mm x 250 mm (excluding air spigots) |
Fresh air and exhaust spigots |
DN 160 |
Room recirculation air spigot |
DN 160 |
Return air (for exhaust) spigot |
DN 160 |
Supply air spigot |
DN 160 |
Weight |
54 Kg |
The product is compliant with the following directives and regulations:
Machinery Directive 2006/42/CE –17 May 2006
Low Voltage Directive 2014/30/EU –26 February 2014
Electromagnetic Compatibility Directive 2014/35/EU - 26 February 2014
RoHS Directive 2011/65/EU –8 June 2011
ErP Directive 2009/125/CE –21 October 2009
PED Directive 2014/68/EU –15 May 2014
Installation environment suitability: Internal environment, civil and industrial use.
AIR FLOWS Renewal mode |
||
Nominal air flow rate |
150 |
m3/h |
Useful supply static pressure* |
290 |
Pa |
Nominal exhaust air flow rate |
150 |
m3/h |
Useful exhaust static pressure* |
330 |
Pa |
AIR FLOWS Air treatment + renewal mode |
||
Nominal air flow rate |
300 |
m3/h |
Nominal recirculation air flow rate |
150 |
m3/h |
Useful supply static pressure* |
240 |
Pa |
Nominal exhaust air flow rate |
150 |
m3/h |
Useful exhaust static pressure* |
330 |
Pa |
AIR FLOWS Air treatment mode only |
||
Nominal recirculation air flow rate |
300 |
m3/h |
Useful recirculation static pressure* |
240 |
Pa |
COOLING AND DEHUMIDIFICATION (1) |
||
Cooling power** |
1,36 |
kW |
Water temperature |
15 |
°C |
Water flow rate |
400 |
l/h |
Pressure drop (including valve) |
17 |
kPa |
Condensation capacity |
31,44 |
l/24h |
HEATING (2) |
||
Total power ** |
1,9 |
kW |
Water flow rate |
400 |
l/h |
Pressure drop (including valve) |
17 |
kPa |
POWER CONSUMPTION (150 m3/h and 200 Pa) |
||
Supply voltage (single-phase HZ) |
230 |
V |
Absorbed power |
0,11 |
kW |
Current |
0,8 |
A |
POWER CONSUMPTION OF UNIT (300 m3/h and 200 Pa) (compressor on) |
||
Supply voltage (single-phase HZ) |
230 |
V |
Absorbed power |
0,33 |
kW |
Current |
3,14 |
A |
(1) Plant water: T = 15°C
ROOM: T= 26°C and R.H. = 60%
FRESH AIR: T = 30°C and R.H. = 60%
Air flows: 150 m3/h recirculation + 150 m3/h fresh air
(2) Plant water: T = 35°C
ROOM: T = 20°C and R.H. = 50%
FRESH AIR: T = -5°C and R.H. = 80%
Air flows: 150 m3/h recirculation + 150 m3/h fresh air
* With G4 Filters
** Coils + Heat exchanger